Products
PRODUCTS DETAILS
Home > Products >
Filter Expansion Tank Plate Heat Exchanger Closed Type Water Cooling System 10-170L/min

Filter Expansion Tank Plate Heat Exchanger Closed Type Water Cooling System 10-170L/min

MOQ: 1
Standard Packaging: Wooden Case
Delivery Period: 30days
Payment Method: T/T
Detail Information
Place of Origin
China
Brand Name
YUDA
Certification
CE ISO9001
Heat Dissipation Power:
10–90 KW
Cooling Medium Flow:
10–170 L/min
Temperature Difference (ΔT):
≥5°C
Cooling Method:
Closed-loop Water Circulation
Maximum Inlet Temperature:
40°C
System Pressure:
1–6 Bar
Pump Type:
Variable Speed Centrifugal Pump
Control Mode:
Automated Temperature And Flow Regulation
Installation:
Floor-mounted With Compact Footprint
Working Medium:
Water, Water-glycol Mixture (optional)
Highlight:

closed type water cooling system

,

170l/min water cooling system

,

170l/min water based cooling system

Product Description
Filter Expansion Tank Plate Heat Exchanger Closed-Type Water Cooling System

Designed specifically for medical nuclear magnetic resonance systems, this closed-type water cooling system ensures optimal performance and reliability in demanding medical environments.

Technical Specifications
  • Frame-cabinet design with strategically placed exhaust and drain valves for easy maintenance
  • Comprehensive system includes main circulating pump, electric three-way valve, filter, expansion tank, plate heat exchanger, and control system
  • Advanced temperature and pressure monitoring with both independent operation and remote control capabilities via terminal or serial port communication
  • Engineered for stability across various working conditions with optimized heat dissipation
  • Constructed with stainless steel and purple copper components for compatibility with deionized water cooling medium
Performance Metrics
Parameter Specification
Heat dissipation power range 10-90 kW
Cooling medium flow range 10-170 L/min
Temperature difference range ≥5℃ between inlet temperature of cooled device and inlet water temperature
Cooling medium Deionized water (external cooling: industrial circulating water)
System static pressure 0.15 MPa
Design pressure 1.0 MPa
Test pressure 1.0 MPa
PH external water coolant 6-9
Key Features

Medical-grade reliability: Specifically designed for nuclear magnetic resonance systems with precise temperature control and stable operation.

Robust construction: High-quality materials ensure compatibility with deionized water and long service life.

Flexible control: Supports both local operation and remote monitoring for integration with medical facility systems.